Transformer Inrush Current Problem
A transformer draws inrush current that can exceed saturation current affecting the magnetic property of the core. This happens even if the transformer is on no load with
its secondary open. The magnitude of the inrush current depends on the instant on the AC wave at which the transformer is switched on.
Figure 1
· If the instant happens to be such that the AC voltage wave is going through its peak value, then there will be no inrush current drawn by the transformer.
The magnitude of the current in this case will be at normal no load value.
· If the instant happens to be such that the AC wave is going through its zero value, then the current drawn will be very high that exceeds the saturation current (see Figure 1).
In this scenario, the transformer has to be protected from inrush current.
Protection of the Transformer
This application note provides a convenient solution (see Figure 2) to deal with the problem of inrush current exceeding saturation current in transformers.
The solution uses NTC Thermistor in series with the primary. This NTC Thermistor offers high resistance at the beginning of switching and limits the inrush current.
After a short time, the NTC Thermistor resistance decreases to a low value due to self heating and does not affect normal operation.
Figure 2
· Each transformer rating: 1000 VA,
· transformer step-down: 30 V
· Total transformer rating: 2000 VA
· Filter capacitors used: 30V, 2300 μF
Prev : NTC Thermistor